Skip to main content

VM-3240VA AMQ

  • VM-3240VAAMQ.jpg
VM-3240VAAMQ.jpg

Voice Alarm System Amplifier

VM-3240VA AMQ

The VM-3000 Series is the world's first Voice Evacuation System complying with both American and Canadian standards UL 2572 and CAN/ULC-S576 listings. It is ideal for small and medium-sized applications. It incorporates such emergency functions as continuous speaker line monitoring and a built-in voice alarm. This easy-to-install system also offers PA broadcasting, paging and BGM functions that ensure consistently high intelligibility. The VM-3000 Series is digitally audio processed and controlled, and may be set up and operated directly by using the controls and LCD display on the front panel. A dedicated PC software configuration capability is also provided for establishing settings via LAN. The incorporation of wide-ranging functional capabilities, superb reliability and versatility make the VM-3000 a highly cost-effective emergency broadcast system.

  • Max. 13 MIC/LINE Inputs
  • Max. 60 assignable speaker zone outputs
  • Up to a combination of 4 Fireman's and remote Microphones
  • Continuous speaker line monitoring without interruption
  • Complete fault detection and indication
  • Built-in voice alarm message
QTY
▼
Power Source
120 V AC, 60 Hz
Power Consumption
Power Consumption 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal)
Rated Output
240 W
Frequency Response
50 Hz - 20 kHz, ±3 dB (at 1/3 rated output)
Distortion
0.7 % or less (at rated output, 1 kHz)
Signal-to-Noise Ratio
85 dB or more
Audio Input/Output Characteristic
Sampling frequency: 48 kHz
A/D D/A converter: 24 bit
Input
Input 1 - 3: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female)/phone jack
Input 4: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, removable terminal block (14 x 2 pins)
BGM 1 - 2: -10 dB*, 10 kΩ, unbalanced, RCA pin jack
External amplifier input: 100 V line, removable terminal block (14 pins)
Output
Speaker output 1 - 2: Max. (240 W) per output
Speaker output 3 - 6: Max. (120 W) per output
Speaker output 1 - 6: Total within 240 W, removable terminal block (14 pins)
Allowable minimum load: 500 Ω (20 W) at 100 V line for speaker line failure detection
Direct output: Direct output from internal or external amplifier, removable terminal block (16 pins)
Recording output BGM/Paging: 0 dB*, 10 kΩ, unbalanced, RCA pin jack
RM Link
Input 1 - 2: Connecting the RM-300MF/RM-200M Remote Microphone. RJ45 female connector
Maximum distance: Total 800 m (874.89 yd) between this unit and remote microphones
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Network I/F
10BASE-T / 100BASE-TX (selectable by automatic negotiation), RJ45 female connector
Maximum distance: 100 m (109.36 yd) between this unit and a switching hub
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
VM Link
Output: Connecting the VM-3240E or VM-3360E, RJ45 female connector
Maximum distance: 800 m (874.89 yd)
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
EXT PA Link
Connecting the VP-2241 or VP-2421, RJ45 female connector
Maximum distance: 5 m (16.4 ft)
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
General Control
Input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, removable terminal block (14 x 2 pins)
Output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: 10 mA or less, removable terminal block (14 x 2 pins)
Emergency Control
Input 1 - 5: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, RJ45 female connector
Input 6: Isolated voltage input, Inactive: -24 V ±20 %, Active: +24 V ±20 %, RJ45 female connector
Status out: Relay contact output, withstand voltage: 40 V DC, operating current: 2 - 300 mA, RJ45 female connector
ATT Control
Relay contact 1-6, 125 V AC or 30 V DC, total under 5 A, removable terminal block (16 pins)
Power Input/Output
Power in: Connecting the VX-2000DS only (operating range: 20 - 40 V DC)
PS out: 28 V DC/18 A
M4 screw terminal, distance between barriers: 11 mm (0.43")
DC24V Output
24 V DC, Maximum feeding current 0.3 A
DS Link
Connecting the VX-2000DS, RJ45 female connector
Maximum distance: 5 m (16.4 ft)
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Operating Temperature
-5 °C to +45 °C (23 °F to 113 °F)
Operating Humidity
5 % to 95 %RH (no condensation)
Finish
Panel: Aluminum, hairline, black
Case: Surface-treated steel plate, black, paint
Dimensions
482 (W) x 132.6 (H) x 431.2 (D) mm (18.98" x 5.22" x 16.98")
Weight
16.5 kg (36.38 lb)
Included Accessories
Power cable (2 m (6.56 ft) ...1, Setting software-CD ...1, Link cable (3 m (9.84 ft) ...2, Plastic foot ...4, Plastic foot mounting screw ...4, Removable terminal plug (14 pins)...3, Removable terminal plug (16 pins) ...1, Emergency microphone (hand-held type) ...1
Optional Accessories
Input transformer: IT-450

Please download Datasheet to access full specifications.

Optional Accessory

  • VM-3240VAAMQ.jpg
VM-3240VAAMQ.jpg

Need other technical materials like software, firmware, or EASE files? Please visit our Download Center.
*Sign-in or membership registration is required.

Get Your Quote.