Skip to main content

VM-3240VA AMQ

  • Voice Alarm System Amplifier
Voice Alarm System Amplifier

Voice Alarm System Amplifier

VM-3240VA AMQ

The VM-3000 Series is the world's first Voice Evacuation System complying with both American and Canadian standards UL 2572 and CAN/ULC-S576 listings. It is ideal for small and medium-sized applications. It incorporates such emergency functions as continuous speaker line monitoring and a built-in voice alarm. This easy-to-install system also offers PA broadcasting, paging and BGM functions that ensure consistently high intelligibility. The VM-3000 Series is digitally audio processed and controlled, and may be set up and operated directly by using the controls and LCD display on the front panel. A dedicated PC software configuration capability is also provided for establishing settings via LAN. The incorporation of wide-ranging functional capabilities, superb reliability and versatility make the VM-3000 a highly cost-effective emergency broadcast system.

  • Max. 13 MIC/LINE Inputs
  • Max. 60 assignable speaker zone outputs
  • Up to a combination of 4 Fireman's and remote Microphones
  • Continuous speaker line monitoring without interruption
  • Complete fault detection and indication
  • Built-in voice alarm message
QTÉ
▼
Source d’alimentation
120 V AC, 60 Hz
Power Consumption
Power Consumption 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal)
Rated Output
240 W
Frequency Response
50 Hz - 20 kHz, ±3 dB (at 1/3 rated output)
Distortion
0.7 % or less (at rated output, 1 kHz)
Signal-to-Noise Ratio
85 dB or more
Audio Input/Output Characteristic
Sampling frequency: 48 kHz
A/D D/A converter: 24 bit
Input
Input 1 - 3: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female)/phone jack
Input 4: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, removable terminal block (14 x 2 pins)
BGM 1 - 2: -10 dB*, 10 kΩ, unbalanced, RCA pin jack
External amplifier input: 100 V line, removable terminal block (14 pins)
Output
Speaker output 1 - 2: Max. (240 W) per output
Speaker output 3 - 6: Max. (120 W) per output
Speaker output 1 - 6: Total within 240 W, removable terminal block (14 pins)
Allowable minimum load: 500 Ω (20 W) at 100 V line for speaker line failure detection
Direct output: Direct output from internal or external amplifier, removable terminal block (16 pins)
Recording output BGM/Paging: 0 dB*, 10 kΩ, unbalanced, RCA pin jack
RM Link
Input 1 - 2: Connecting the RM-300MF/RM-200M Remote Microphone. RJ45 female connector
Maximum distance: Total 800 m (874.89 yd) between this unit and remote microphones
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Network I/F
10BASE-T / 100BASE-TX (selectable by automatic negotiation), RJ45 female connector
Maximum distance: 100 m (109.36 yd) between this unit and a switching hub
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
VM Link
Output: Connecting the VM-3240E or VM-3360E, RJ45 female connector
Maximum distance: 800 m (874.89 yd)
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
EXT PA Link
Connecting the VP-2241 or VP-2421, RJ45 female connector
Maximum distance: 5 m (16.4 ft)
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
General Control
Input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, removable terminal block (14 x 2 pins)
Output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: 10 mA or less, removable terminal block (14 x 2 pins)
Emergency Control
Input 1 - 5: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, RJ45 female connector
Input 6: Isolated voltage input, Inactive: -24 V ±20 %, Active: +24 V ±20 %, RJ45 female connector
Status out: Relay contact output, withstand voltage: 40 V DC, operating current: 2 - 300 mA, RJ45 female connector
ATT Control
Relay contact 1-6, 125 V AC or 30 V DC, total under 5 A, removable terminal block (16 pins)
Power Input/Output
Power in: Connecting the VX-2000DS only (operating range: 20 - 40 V DC)
PS out: 28 V DC/18 A
M4 screw terminal, distance between barriers: 11 mm (0.43")
DC24V Output
24 V DC, Maximum feeding current 0.3 A
DS Link
Connecting the VX-2000DS, RJ45 female connector
Maximum distance: 5 m (16.4 ft)
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Operating Temperature
-5 °C to +45 °C (23 °F to 113 °F)
Operating Humidity
5 % to 95 %RH (no condensation)
Finish
Panel: Aluminum, hairline, black
Case: Surface-treated steel plate, black, paint
Dimensions
482 (W) x 132.6 (H) x 431.2 (D) mm (18.98" x 5.22" x 16.98")
Weight
16.5 kg (36.38 lb)
Included Accessories
Power cable (2 m (6.56 ft) ...1, Setting software-CD ...1, Link cable (3 m (9.84 ft) ...2, Plastic foot ...4, Plastic foot mounting screw ...4, Removable terminal plug (14 pins)...3, Removable terminal plug (16 pins) ...1, Emergency microphone (hand-held type) ...1
Optional Accessories
Input transformer: IT-450

Veuillez télécharger la fiche technique pour accéder aux spécifications complètes.

Accessoire(s) optionnel(s)

Please sign in to access further technical materials such as software, firmware or EASE files.

Get Your Quote.